Backup power: how to choose an inverter and a battery

Sizing backup power comes down to four numbers: the load power, the starting current, the hours you need and the system voltage. Below: a table of typical loads, formulas for the inverter and the battery in Wh and Ah at 12, 24 and 48 V, LiFePO4 compared with gel, and an example for a flat over 8 hours.

Where to start: the list of loads

List everything that has to keep running during an outage, with its actual power draw — from the data sheet or the rating label on the case. For motors and compressors, account separately for the starting current: at start-up they draw 2–3 times their rated power for about a second.

LoadPower, WStartNote
Router and optical terminal10–20—Runs continuously
LED lighting for a flat40–80—5–8 luminaires of 8–10 W
Laptop45–90—Charging plus use
Television60–150—Depends on the screen size
Gas boiler with circulation pump80–150×2Sensitive to the waveform and to phasing
Refrigerator100–200×3The compressor runs in cycles
Desktop computer with monitor200–400—Gaming machines draw more
Water supply pump500–1 000×3The highest starting current
Microwave oven1 000–1 300—Draws more than the figure on the door
Electric kettle, water heater, heater1 500–2 500—Usually left off the backup: they drain the battery within an hour

Inverter power

The inverter must carry the sum of the continuous loads with a margin and withstand the start of the largest motor.

Pinv = ΣP × 1.25, where ΣP is the total power of the loads switched on at the same time. The 25 % margin covers heating, inaccuracy in the data sheet figures and new appliances.

Ppeak = ΣP + Pmotor × (k − 1), where k is the starting factor of the most powerful motor. The inverter’s peak power (listed separately in the data sheet, usually twice the rated power for a few seconds) must be no lower than Ppeak.

Other requirements: a pure sine wave — for a boiler, a fridge, pumps and any equipment with a motor or a switch-mode power supply; a modified sine wave suits only lamps and chargers. For a boiler — correct output phasing (phase and neutral are not swapped) and a transfer time of no more than 10–20 ms if the inverter works in UPS mode.

Battery capacity: Wh and Ah

A battery is sized by energy, not by power. First, how many watt-hours have to be delivered; then, how many ampere-hours that means at the chosen voltage.

E = ΣP × t ÷ η ÷ DoD, where t is the hours of autonomy, η is the inverter efficiency (0.9), DoD is the working depth of discharge: 0.9 for LiFePO4, 0.5 for gel and AGM.

C = E ÷ U, where U is the system voltage: 12, 24 or 48 V. The result is in ampere-hours.

Energy required, E12 V24 V48 V
1 000 Wh83 Ah42 Ah21 Ah
2 000 Wh167 Ah83 Ah42 Ah
4 000 Wh333 Ah167 Ah83 Ah
8 000 Wh667 Ah333 Ah167 Ah

The system voltage follows the inverter power: up to 1–1.5 kW — 12 V, 2–3 kW — 24 V, from 3–5 kW — 48 V. The higher the voltage, the lower the current in the cables: 3 kW at 12 V means 250 A and cable from 70 mm², at 48 V — 63 A and 16 mm².

LiFePO4 or gel and AGM

ParameterLiFePO4Gel / AGM
Working depth of discharge80–90 %50 %
Service life3 000–6 000 cycles500–800 cycles
Weight per 1 kWh10–12 kg25–30 kg
Charging rate0.5–1C, 1–2 hours0.1–0.2C, 8–10 hours
Operation in frostDischarge down to −20 °C, charging only above 0 °C (the BMS blocks it)Works, but capacity drops by 30–50 %
Price per kWhHigher up frontLower up front
Price per cycle3–5 times lowerHigher

Gel makes sense for occasional outages and small UPS units where the battery stays charged for years. For daily cycling choose LiFePO4: it delivers twice as much from the same rated capacity and lasts 5–8 times longer.

Charging and solar panels

The battery has to recharge between outages. The charging current of a hybrid inverter is usually 20–60 A; a 48 V 100 Ah battery charges from empty at 40 A in 2.5–3 hours, a gel battery of the same size takes 8–10 hours at a low current.

Solar panels reduce dependence on the outage schedule: 1 kW of panels yields 4–5 kWh a day in summer and 1–1.5 in winter. Panels need an MPPT controller or a hybrid inverter with a PV input; the voltage and current of the panel array are checked against the input range.

Example: a flat over 8 hours

Load: router 15 W + lighting 60 W + laptop 65 W + boiler with pump 120 W + fridge 150 W = 410 W.

Inverter: 410 × 1.25 = 513 W. Peak: 410 + 150 × (3 − 1) = 710 W. A 1 000 W pure sine wave inverter with a 2 000 W peak meets both conditions.

Energy for 8 hours: 410 × 8 ÷ 0.9 = 3 644 Wh (the fridge runs in cycles, so the real figure is lower — we calculate with a margin).

LiFePO4: 3 644 ÷ 0.9 = 4 050 Wh → 12 V: 337 Ah; 24 V: 169 Ah; 48 V: 84 Ah. The practical choice is 24 V 200 Ah or 48 V 100 Ah (5.1 kWh): both leave a reserve for a long evening.

Gel: 3 644 ÷ 0.5 = 7 288 Wh → 12 V: 607 Ah, that is, six 100 Ah batteries weighing about 180 kg. That is why lithium is used for daily autonomy.

Common mistakes

  • An inverter sized for the average rather than the peak load — the fridge does not start, the inverter goes into protection.
  • A modified sine wave on a boiler or a pump — hum, overheating, electronics failures.
  • A gel battery run down “to zero” — it loses service life after a few dozen deep cycles.
  • Thin cables at 12 V — heating, voltage drop, emergency shutdown under load.
  • Parallel connection to the grid without an ATS (automatic transfer switch) or a changeover switch — dangerous for electricians working on the line, and prohibited.

Calculation

How much inverter and battery you need

Switch on what has to keep running during an outage and say for how many hours. You get the inverter power and the battery capacity.

Технічне приміщення з гібридним інвертором і стійкою акумуляторів LiFePO4

We size the inverter with a 25 % margin over the total load and check it against the starting currents of the fridge and pumps. Capacity assumes 90 % inverter efficiency and a working depth of discharge of about 90 % for LiFePO4 and 50 % for gel and AGM batteries.