Industrial lighting: illuminance levels and calculation

Lighting for a workshop or a warehouse is calculated from the required level in lux, not from “watts per metre”. Below: typical levels under DBN V.2.5-28 (the Ukrainian lighting standard), the utilisation factor method with its formula, choosing a luminaire by ceiling height, IP and IK requirements and a worked example for a 30 × 18 m warehouse with an 8 m ceiling.

  • 6 minutes read
  • newsuper.shop team

Illuminance levels

The required level depends on the category of the visual task — the size of the detail to be seen, its contrast and the background — so within one workshop it can differ by a factor of two depending on the operations. The table gives typical ranges for a preliminary calculation; check the final value against the current edition of DBN V.2.5-28 “Natural and Artificial Lighting” and the process engineer’s brief.

AreaTypical illuminanceReference plane
Warehouse: storage, aisles75–200 lxFloor
Warehouse: picking, goods-in200–300 lxWorking plane 0.8 m
Production: rough work, assembly of large units200 lxWorking plane
Production: medium precision, machining, assembly300–500 lxWorking plane
Production: precision work, quality control500–750 lx and aboveWorking plane, often with local lighting
Workshop, repair area, car service station300–500 lxWorking plane
Office, design office300–500 lxDesk 0.8 m
Corridors, stairs, plant rooms50–100 lxFloor
Covered car park75 lxFloor

Besides average illuminance, the standard sets uniformity (the ratio of minimum to average no lower than 0.4–0.6 in work areas), the glare rating (UGR up to 22–25 for workshops, up to 19 for offices) and the flicker factor — up to 5–10 % where there are rotating machines: flickering light creates a stroboscopic effect and can make a spindle or a shaft look “stationary”.

The utilisation factor method

For uniform general lighting, the number of luminaires is calculated by the luminous flux utilisation factor method.

N = E × S × ks ÷ (Φ × η), where E is the required illuminance, lx; S is the area, m²; ks is the safety factor for dirt and ageing (1.2 for clean rooms, 1.4–1.5 for dusty workshops and warehouses); Φ is the luminous flux of one luminaire, lm; η is the utilisation factor, the share of the flux that reaches the working plane.

η depends on the room index and on the reflectance of the ceiling, walls and floor. i = a × b ÷ (h × (a + b)), where a and b are the length and the width, h is the height from the luminaire to the working plane. Guide values for LED luminaires with a wide distribution:

Index iLight surfaces (70/50/20)Dark surfaces (50/30/10)
0.6–0.80.35–0.450.25–0.35
1.0–1.250.45–0.550.35–0.45
1.5–2.00.55–0.650.45–0.55
2.5–3.00.65–0.750.55–0.60
4.0–5.00.75–0.800.60–0.70

With narrow high-bay optics at a great height η is higher, but uniformity is worse: the beams of neighbouring luminaires must overlap. An exact result comes from a DIALux calculation with the manufacturer’s IES files; the formula above is there to check a commercial quotation and avoid buying twice as much, or half as much, as you need.

Luminaire by ceiling height

Mounting heightLuminaire typeFlux per unitSpacing
Up to 4 mLinear LED 36–72 W, 1.2–1.5 m long, in rows4 000–9 000 lmDistance between rows ≈ 1.0–1.2 h
4–6 mHigh-output linear luminaires or trunking lines8 000–15 000 lm≈ 1.0 h
6–12 mSuspended high-bay 100–200 W, beam angle 60–90°13 000–28 000 lm≈ 0.8–1.0 h for 90°, 0.6–0.8 h for 60°
Over 12 mHigh-bay 200–300 W with narrow 40–60° optics26 000–42 000 lmBy a DIALux calculation

Efficacy is 130–160 lm/W for current industrial series and 90–110 lm/W for budget ones. On old lines with T8 fluorescent tubes, switching to T8 LED tubes gives the same level at half the power without replacing the housings — after checking the wiring diagram.

IP, IK, temperature and colour

  • IP65 — dust and water jets: workshops with wet cleaning, wash bays, dusty warehouses, canopies. IP54 is enough for dry heated rooms. IP66–IP67 — pressure washing, food production.
  • IK08–IK10 — impact resistance for forklift routes, sports halls and low mounting heights; for an 8 m ceiling IK06–IK08 is enough.
  • Temperature — a driver is rated for −20…+40 °C; hot workshops and spaces under the roof in summer need series rated up to +50…+60 °C, otherwise service life halves with every 10 °C.
  • Colour temperature — 4000–5000 K for production and assembly, 5000–6500 K for warehouses and inspection where contrast matters; 4000 K where people work a full shift.
  • CRI — from 80 for general lighting, from 90 for painting, textiles, quality control and food production.
  • Flicker — up to 5 % for workshops with machine tools; look for a “flicker free” mark or the flicker factor in the data sheet.

Emergency lighting

Escape lighting and “Exit” signs are a mandatory part of the design. Guide values under DSTU EN 1838 (the Ukrainian adoption of EN 1838): at least 1 lx along the centre line of an escape route, 0.5 lx in open areas, 5 lx at fire-fighting equipment and first-aid kits; the duration is usually 1 hour, 3 for large sites. Signs go above every exit and at turns of the route, visible from any point. The requirements for a specific site are set by the current DBN (Ukrainian building codes) and the fire-safety design.

Example: a 30 × 18 m warehouse with an 8 m ceiling

Given: a warehouse with racking and aisles, required level E = 150 lx on the floor, area S = 30 × 18 = 540 m², light walls and ceiling, moderate dust — ks = 1.4. The luminaires are suspended at 7.5 m; the working plane is the floor, h = 7.5 m.

Room index: i = 540 ÷ (7.5 × 48) = 1.5 → for light surfaces η ≈ 0.55.

Required flux: Φtotal = 150 × 540 × 1.4 ÷ 0.55 = 206 000 lm.

Option 1 — high-bay 150 W, 15 000 lm, 5000 K, IP65: N = 206 000 ÷ 15 000 = 13.7 → 14 luminaires, two rows of 7 over the aisles, about 4.3 m apart in a row and 9 m between the rows (no light is needed over the racks). The installed power is 2.1 kW, the power density 3.9 W/m².

Option 2 — linear 72 W, 9 000 lm: N = 206 000 ÷ 9 000 = 23 luminaires at a height of 8 m — more uniform, but more mounting points and more cable; justified at heights up to 5–6 m.

Uniformity check: for 90° optics, a 4.3 m spacing at h = 7.5 m is 0.57 h, a good overlap. The 9 m between the rows is 1.2 h: illuminance will dip over the racks, which is acceptable for storage; if there are work areas between the rows, add a third row or use 200 W luminaires.

Common mistakes

  • Calculating in watts per metre — LEDs of different quality give anything from 90 to 160 lm/W; calculate lumens and lux.
  • No safety factor — after two years of dust and degradation, illuminance drops by 20–30 % and the standard is no longer met.
  • Narrow optics under a low ceiling — pools of light with dark bands between them; up to 6 m take 90–120°.
  • IP20 in a dusty workshop — dust on the board and the lenses, overheating, failure within a year.
  • Flickering light over machine tools — a stroboscopic effect and injuries; check the flicker factor.